Navigation
SBi
Danish Building
Research Institute
Dr. Neergaards Vej 15
DK - 2970 Hørsholm
Denmark
sbi@sbi.dk
Tel +45 45 86 55 33
Fax +45 45 86 75 35
CVR-No. 29102384
Publication with English Summary

Settling of loose-fill insulation materials in walls

Summary

The report describes material behaviour, which significantly influences the settling of loose-fill insulation materials. The specific application presented here is loose-fill insulation material injected in walls as thermal insulation.
The physical formulation of the issue to be discussed is that the mass is kept in position in the cavity by frictional forces, which counteracts the settling but complicates injection. The purpose of this study is to investigate whether there is a possibility that decreased friction will be able to release settling.
Cellulose loose-fill material injected in a 0.1 m thick and 1 m wide gypsum wall with a minimum density of 48 kg/m3 was found not to settle if kept at a constant relative humidity, RH 50 %. A minimum density of 53 kg/m3 is necessary if the thickness of the wall is increased from 0.1 m to 0.3 m. If changing the constant environment from RH 50 % to RH 80 % a minimum density of 63 kg/m3 is necessary. Results are shown in figure 1.
Furthermore, results so far show that cellulose loose-fill material spread on the attic floor will have a density after settling of 48 kg/m3 for a constant RH 50 %, corresponding to 43 kg/m3 dry material. The results were found by using a model and tests.

Model

The report describes a theory that can be applied to estimate the settling of loose-fill insulation materials. Settling is determined from characteristics describing the wall and the relative humidity of the loose-fill material and the density of the loose-fill material in the wall. In addition a model describing the creep of the loose-fill material is presented.
Furthermore, it was found that injection procedures for loose-fill materials can be evaluated. When evaluating the injection process, the relationship between stresses and the distance from the injection point must be calculated for each wall and insulation material. From these calculations the injection procedures can be optimised to achieve an almost homogeneous distribution of the insulation material in the wall.

Tests

The friction coefficient is determined from tests for a combination of 3 - 4 wall materials and 7 loose-fill materials. The loose-fill materials tested are both new and conventional materials sold on the Danish market and used as thermal insulation. The various types of loose-fill material include; mineral based, cellulose, mineral granulate, woodwool and granulated flax.
The ratio between the horizontal pressure and the vertical pressure is determined for all the materials. The ratio is difficult to measure but it was nevertheless done with success. The test method is described in the report.
For a number of the materials, creep has been described. Tests were carried out at a constant temperature. Tests include three load cases, including 80 Pa, 200 Pa and 500 Pa, with different combinations of loose-fill density and a relative humidity of either 50 % or 80 %. Furthermore, creep tests were carried out using a constant temperature and a constant load level for RH ranging from 50 % to 80 %.
Two full-scale walls were used to verify the model.

Calculations

A large number of calculations were performed by applying the presented model. Calculations show that stresses in loose-fill materials can be determined.
It was found to be possible to determine creep analytically with good agreement with test results.

Conclusion

A model is presented which considers stress analysis for loose-fill materials to remain in a stress-stable state, and the creep of the material. From stress analysis it was found to be possible to set up equations to estimate stresses in granulated insulation materials as a function of the height of a wall. These considerations are combined with theories describing creep of a material, thus providing a better understanding of the material behaviour of loose-fill insulation materials in walls.
In addition a method is presented for theoretically estimating the necessary density of loose-fill insulation in walls in order to ensure volume stability. This theory can be used to calculate the density needed for a given granulated insulation material to stay in a volumestable state.

Graph showing calculated necessary density as a function of wall thickness

Figure 1. Calculated necessary density as a function of wall thickness to prevent settling of cellulose loose-fill material in a wall. Calculations are performed for a 0.1 m wide gypsum wall with a relative humidity equal to 50 % and 80 %. Data from Ekofiber vägg are used. The calculated volume-stable state is related to RH 50 % and 23 oC. The curve for RH 80 % is partly based on extrapolated data.

By og Byg documentation 011. Torben Valdbjørn Rasmussen.

You can download the publication free of charge:

PDF version (1,6 MB)

Published 18.07.2001
Last edited 09.03.2006 by Hanne Brix